5 lss (layer setting services) – Baumer BA_DSRT_22DJ Benutzerhandbuch
Seite 54

Manual_CANopen_StrainLink_EN_V3_05.doc
54/65
Baumer
22.07.11/dam
Frauenfeld, Switzerland
7.5 LSS (Layer setting services)
7.5.1
Printed LSS information on the sensor
To use the LSS functionality LSS data, which clearly identifies the sensor, is needed. The data are stored in
the identity object (object 1018h). This data is printed on every sensor.
Example of a printed sensor with LSS information:
Title:
Description:
Index:
Sub-index:
VenID
Vendor-ID
1018h
01h
ProdC
Product code
1018h
02h
RevNr
Revision number
1018h
03h
SerNr
Serial number
1018h
04h
7.5.2
Address the sensor with LSS
There are two possibilities to communicate with the sensor by LSS. The LSS service supports sensors in an
existing network but also sensors with a master.
In both cases the bus has to be brought in stop mode.
In LSS mode the sensors are addressed with ID 7E5h. The respond is with ID 7E4h.
Bring all sensors to stop mode:
ID
DLC
Byte1
Byte2
0
2
02h
00h
LSS data are displayed in
decimal number system.