Baumer BA_DSRT_22DJ Benutzerhandbuch

Seite 41

Advertising
background image

Manual_CANopen_StrainLink_EN_V3_05.doc

41/65

Baumer

22.07.11/dam

Frauenfeld, Switzerland

6.4.4

Autozero

The autozero function (Objekt 2003h) contains the same mechanism as the procedure in the object 6125h,
except that the object 2003h cannot be mapped to the Receive PDO. The Receive PDO has a fixed mapping
and cannot be modified.

6.4.5

Status autozero

The object 2004h contains the status of the tare procedure with Receive PDO. This object can be mapped
and is configured to the Transmit PDO3 by default. Is PDO3 enabled, the feedback about the status of the
tare function is given.

00’00h no tare procedure with Receive PDO is done since start up

75’00h („u“ in ASCII) a tare procedure is executing

66’00h („f“ in ASCII) the last tare procedure is completed successfully

65’72h („er“ in ASCII) the last tare procedure is failed

6.4.6

Baud rate

The baud rate specifies the speed at which the whole bus is operated. All users must have the same baud
rate. The CANopen strain link is shipped with 125kBaud.

Read baud rate (object 2100h):

ID

DLC

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Byte7

Byte8

600h + ID

8

40h

00h

21h

00h

0

0

0

0


Response from CANopen strain link:

ID

DLC

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Byte7

Byte8

580h + ID

8

4Fh

00h

21h

00h

03h

0

0

0


Byte 5:

00h

10 kBaud

04h

250 kBaud

01h

20 kBaud

05h

500 kBaud

02h

50 kBaud

06h

800 kBaud

03h

125 kBaud

07h

1000 kBaud



Function mode:
Changing baud rate:













PWR-On Reset /

NMT Reset

New
Baudrate

Old
Baudrate

Boot up Message

Stroe Parameter

(Index 1010)

Change Baudrate

(Index 2100)