2 Project engineering

2.1 Maximum system extent

To construct an operational bus, there must be at least one master (or parent system) on the bus. This
master may be a PLC controller or a PC with an appropriate CAN board. Every CANopen strain link
represents one active CAN node.
One bus string with one master of the CAN network can have a maximum of 127 users. Every user has its
own address.

You can find the factory defaults of this sensor in Chapter 6.2

Parameter Handling (save, load default)

.


You must absolutely comply with the permissible bus and stub line lengths given in Table 1.

The maximum permitted total line length and total stub length

is dependent on the baud rate and

can be divided into several segments or individual stubs.


Table 1

Baud rate [Kbit/s]

10

20

50

100

125

250

500

800

1000

Total bus length

5,000 m

3,000 m

1,000 m

500 m

400 m

200 m

75 m

30 m

25 m

Total stub length

1,360 m

875 m

350 m

175 m

140 m

70 m

35 m

20 m

17 m

Individual stub length

270 m

175 m

70 m

35 m

28 m

14 m

7 m

4 m

3 m

Maximum total bus length (with 120 ohm termination resistor) and maximum stub length (without termination
resistor) as a function of the baud rate