2 Project engineering
2.1 Maximum system extent
To construct an operational bus, there must be at least one master (or parent system) on the bus. This
master may be a PLC controller or a PC with an appropriate CAN board. Every CANopen strain link
represents one active CAN node.
One bus string with one master of the CAN network can have a maximum of 127 users. Every user has its
own address.
You can find the factory defaults of this sensor in Chapter 6.2
Parameter Handling (save, load default)
.
You must absolutely comply with the permissible bus and stub line lengths given in Table 1.
The maximum permitted total line length and total stub length
•
is dependent on the baud rate and
•
can be divided into several segments or individual stubs.
Table 1
Baud rate [Kbit/s]
10
20
50
100
125
250
500
800
1000
Total bus length
5,000 m
3,000 m
1,000 m
500 m
400 m
200 m
75 m
30 m
25 m
Total stub length
1,360 m
875 m
350 m
175 m
140 m
70 m
35 m
20 m
17 m
Individual stub length
270 m
175 m
70 m
35 m
28 m
14 m
7 m
4 m
3 m
Maximum total bus length (with 120 ohm termination resistor) and maximum stub length (without termination
resistor) as a function of the baud rate