2 project engineering, 1 maximum system extent – Baumer BA_DSRT_22DJ Benutzerhandbuch

Seite 6

Advertising
background image

Manual_CANopen_StrainLink_EN_V3_05.doc

6/65

Baumer

22.07.11/dam

Frauenfeld, Switzerland

2 Project engineering

2.1 Maximum system extent

To construct an operational bus, there must be at least one master (or parent system) on the bus. This
master may be a PLC controller or a PC with an appropriate CAN board. Every CANopen strain link
represents one active CAN node.
One bus string with one master of the CAN network can have a maximum of 127 users. Every user has its
own address.

You can find the factory defaults of this sensor in Chapter 6.2

Parameter Handling (save, load default)

.


You must absolutely comply with the permissible bus and stub line lengths given in Table 1.

The maximum permitted total line length and total stub length

•

is dependent on the baud rate and

•

can be divided into several segments or individual stubs.


Table 1

Baud rate [Kbit/s]

10

20

50

100

125

250

500

800

1000

Total bus length

5,000 m

3,000 m

1,000 m

500 m

400 m

200 m

75 m

30 m

25 m

Total stub length

1,360 m

875 m

350 m

175 m

140 m

70 m

35 m

20 m

17 m

Individual stub length

270 m

175 m

70 m

35 m

28 m

14 m

7 m

4 m

3 m

Maximum total bus length (with 120 ohm termination resistor) and maximum stub length (without termination
resistor) as a function of the baud rate