Manual_CANopen_StrainLink_EN_V3_05.doc

38/65

Baumer

22.07.11/dam

Frauenfeld, Switzerland

Change interrupt delta input (object 7133h):

ID

DLC

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Byte7

Byte8

600h + ID

8

22h

33h

71h

01h

F4h

01h

0

0

Interrupt delta input value: 5 µ

ε

5 * 10

2

= 500 = 01’F4h

Byte 4:

01h

Sub-index 1

value for PDO1

Byte 5 + 6:

F4’01h

01’F4 (LSB first)

500


Response from CANopen strain link:

ID

DLC

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Byte7

Byte8

580h + ID

8

60h

33h

71h

01h

0

0

0

0


If the value 0 is written into the object 7133h, the delta value function will be switched off.

Read interrupt delta input (object 7133h):

ID

DLC

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Byte7

Byte8

600h + ID

8

40h

33h

71h

01h

0

0

0

0


Response from CANopen strain link:

ID

DLC

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Byte7

Byte8

580h + ID

8

4Bh

33h

71h

01h

F4h

01h

0

0

Byte 5 + 6:

F4’01h

01’F4 (LSB first)

500

5 µ

ε


The interrupt delta input object of the 24bit process value (object 8133h) is according to the object 7133h
except the data length of the value (24bit instead of 16bit).